Xiamen Hengxiang Refrigeration Equipment Co., Ltd.

Need-based integrity / A good reputation to have good communication with customers convenient transactions

Manufacturer from China
Site Member
4 Years
Home / Products / Commercial Refrigeration Repair Parts /

Digital Electronic Double Pressure Gauge Manifold For Refrigerant

Contact Now
Xiamen Hengxiang Refrigeration Equipment Co., Ltd.
Province/State:fujian
Country/Region:china
Contact Person:MrsIris
Contact Now

Digital Electronic Double Pressure Gauge Manifold For Refrigerant

Ask Latest Price
Brand Name :HengXiang
Model Number :SBF-L07
Certification :ISO9001、ISO17025、ISO14001、ISO14001、ISO 45001
Place of Origin :China
MOQ :100 Sets
Price :Negotiable
Payment Terms :T/T
Supply Ability :400000 Sets per Month
Delivery Time :30 Working days
Packaging Details :Export stanard box and carton
Material :Brass
Color :Green
Type :Manifold Pressure Testing
Application Refrigerants :R12;R22;R410A;R502;R134A etc.
Customized Support :OEM, ODM
Warranty :1 Year
Delivery Support :By Sea or by Air
Loading Port :Ningbo or Shanghai
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Digital Electronic Double Pressure Gauge Manifold as refrigerant equipment, AC and Refrigerant Tools SBF-L07

Product Functions

1.Widely used in the area of hydraulic and atmospheric pressure as refrigerant equipment, air conditioner and refrigerant tools , pressure tools, vacuum equioment, pneumatic equipment,etc.

2.This gauge has no moving parts, has long service life, high precision, good long-term stability.

3.It has pressure and temperature parameters for commonly used refrigerant inside,the measured pressure, condensation temperature and evaporation temperature are very clear to see.

Digital Electronic Double Pressure Gauge Manifold For Refrigerant

Application Range

The SBF-L-07 digital display double table valve is used for the assembly and maintenance of vacuum refrigeration system. The operator must possess the qualification of the industry and have certain operational experience.

◆ The SBF-L-07 digital display double table valve sets together with the traditional composite table, the temperature measuring instrument and the refrigerant characteristic diagram, and it's available to measure both pressure and temperature.

◆ The SBF-L-07 digital display double table valves are suitable for most non-corrosive refrigerant, water, alcohols. But it is not suitable for the refrigerant containing ammonia.

◆ This product is not suitable for the areas with explosion - proof requirements.

Highlight: Strong, shockproof &corrosion-resistant,Clear and direct reading

Features and
parameters
Value
Measure
parameters
Pressure: MPa,kPa,bar,psi,kgf/cm ,inHg
Temperature: F ,ºC,K
Sensor Pressure: internal pressure sensor×2
Temperature: external temperature sensor×2
Port Pressure: 1/4" SAE x 3
Temperature: USBx2
Measure range Pressure: -0.1~5.0Mpa
Temperature: -55~125ºC
Resolution Pressure: 0.001MPa
Temperature: 0.1ºC
Measure
accuracy
Pressure: ±0.4% (below 20±5ºC)
Temperature: ±0.5ºC
Measure frequency 1s
Features and parameters Value
Applicable refrigerant type 82 kinds
Optional refrigerant

R11,R113,R114,R115,R116,R12,R123,R124,R1234yf,R1234ze,R125,R1270,R13,R134A,R14,R141B,R142B,

R143A,R152A,R161,R22,R227,R23,R290,R32,R401A,R401B,R401C,R402A,R402B,R404A,R406A,R407A,R407B,

R407C,R407D,R408A,R409A,R409B,R410A,R410B,R411A,R411B,R412A,R413A,R414A,R414B,R415A,R415B,

R416A,R417A,R418A,R419A,R420A,R421A,R421B,R422A,R422B,R422C,R422D,R423A,R424A,R425A,R426A,

R427A,R428A,R434A,R437A,R438A,R50,R500,R501,R502,R503,R504,R507A,R508A,R508B,R509A,R600,R600A,

R744

Note: The mersure of R32,R744 cannot beyond the specified mersuring range

Unapplicable refrigerant Ammonia (R717)and ammonia
- containing refrigerant.
Ambient humidity 10%~90% RH
Allowable overload pressure 110% measuring range
Operating temperature -10~50ºC
Material Double color engineering plastics.
Dimension 185x110x55mm
Weight About 0.5Kg
Power supply AA Alkaline?batteries, 1.5Vx4
(Battery life: >2000 hours, backlight extinction).
Display LCD screen with backlight.
Protection degree IP42
Adopted standard JB/T 7392-2006

Digital Electronic Double Pressure Gauge Manifold For Refrigerant

Inquiry Cart 0